Release note firmware for smart/Industrial 6 series (beginning with SN 160000) ============ Summary of changes between firmware versions. Legend: + Added functionality - Removed functionality * Changed functionality ! Bugfix to learn more about your hardware/firmware version, how to upgrade or downgrade... see: https://www.voegtlin.com/data/vog-get-red-y-faq-hw-fw.pdf ***************** HW ≥ 6.0.5 / SN ≥ 400000 ***************** Version 6.2.03 ============== ! Fix ProfiBus power-cycle problem ! Fix sporadic device reset/reboot in rare cases Version 6.2.02 ============== * Improved PID behavior on leaving valve protection mode ! Warning "no flow" not properly delayed by plausibility time Version 6.2.01 ============== * Support new Hardware version 6.0.5 ! Bad startup PID behavior for some pressure control setups ! Bad "no flow" warning during valve protect ! Setpoint not reached warning not working as expected * Improved EMI ***************** HW ≥ 6.0.0 / SN < 400000 ***************** Version 6.1.14 ============== ! Bad "no flow" warning during valve protect ! Setpoint not reached warning not working as expected * Improved EMI Version 6.1.13 ============== ! Totalizer "ghost flow" on startup ! Bad samples on ADC startup Version 6.1.12 ============== * Improve PID behavior with setpoint near low cutoff ! After installing the firmware 6.1.11 update, the Profibus communication got disabled. The phenomenon has been fixed ! Suppress rare spikes in sensor raw data by adjusting CPU load and ADC startup time Version 6.1.11 ============== + Added new registers for new product order code (POC): 0x0404/0x040A ! Hardware 6.03 issue while analog control in lower range area Version 6.1.10 ============== not released, internal tests Version 6.1.09 ============== ! In very rare cases the valve can be opened for about 1 minute directly after power-up. While in that state the valve can’t be controlled by PID control. ! Smart can fail to detect display module after it is powered once without a display module connected. Version 6.1.08 ============== + PNEC functionality: Firmware supports external Hardware for Profinet/Ethercat communication Version 6.1.07 ============== not released, internal tests Version 6.1.06 ============== + fast temperature filtering: Customer specific Temperature filtering is configurable Version 6.1.05 ============== + Timeout Features: behaviour of the instrument in case of communication loss is configurable